| Technical parameter | Technical index | |
| Power parameter | Current | Scope: 0.030~6A, precision: 0.2% |
| Voltage | Scope: 9~400V, precision: 0.2% | |
| Active power | Scope: 0 ~ 99999999kw, precision: 0.5% | |
| Reactive power | Scope: 0 ~ 99999999kvar, precision: 0.5% | |
| Power factor | Scope: 0 ~ 0.99, precision: 0.5% | |
| Frequency | Scope: 40-60Hz, precision: + 0.01Hz | |
| Active energy | Scope: 0~99999999 Mwh, precision: 0.5% | |
| Reactive energy | Scope: 0~99999999 Mvarh, precision: 1.0% | |
| Apparent energy | Scope: 0~99999999 Mvarh, precision: 0.5% | |
| Power pulse output | Pulse output interface (apolegamy) | |
| Metering voltage | Three phase four wire 3×57.7V , 3×220V | |
| Basic current (Ib) | 1A, 5A, | |
| Connection mode | Three phase four wire, scott wiring | |
| Input parameter | Passive dry contact | |
| Relay output | Passive normally open contact, contact capacity: AC220V/5A, DC30V/5A | |
| Analog output | 4~20mA | |
| Communication parameter | Communication interface | RS485 interface |
| Communication protocol | Protocol between Modbus_RTU and DLT645-2007 | |
| Baud rate | 1200bps,2400 bps,4800 bps,9600 bps | |
| Data format | 8 data bits, 1 stop bits, no proof | |
| Pause test | Response time | ≤4s ≤4s |
| Retention time | ≥10 years | |
| Operational environment | Ambient temperature | -10°C to +55°C (regular work) |
| Ambient humidity | ≤95% | |
| Atmospheric pressure | 80~110KPa | |
| Altitude | ≤2500 meters | |
| Working power supply | Power supply | AC85~265V/DC110~370V |
| Power consumption | ≤5W | |
| Isolation pressurization | 2KV | |
| Power drop | 200ms | |
| Insulating property | Electrical strength | More than AC2000V between the shell and the terminal |
| Insulating property | More than 100ΜΩbetween the shell and the terminal | |
| Shock resistance | 10~55~10Hz 2g 1min | |
| Anti-interference | Coincidence with GB/ t17626.8-1998 standard | |
| Installation | Embedded installation | |