| US$435.00-1,045.00 | 1 Piece (MOQ) |
| General | |
| Topology | On-line double conversion with PFC (Power Factor Correction) system |
| Configuration | Rack/Tower |
| Part Number | 9PX5Ki |
| Rating (VA/Watts) | 5000/4500 |
| Dimensions (H x W x D, mm) | 130 (3U) x 440 x 685 |
| Weight (kg) | 48 |
| Warranty | 3 years on electronics, 2 years on battery |
| Electrical Input | |
| Connection | Hardwired - see manual for terminal block layout |
| Input Voltage Range | 176-276V without derating (up to 100-276V with derating) |
| Nominal Voltage | 200/208/220/230/240V |
| Frequency | 50/60 Hz autoselection |
| Frequency Range | 40-70 Hz |
| Short Circuit Current | 90 A |
| THDI | <5% |
| Electrical Output | |
| Voltages | 200/208/220/230/240V +/- 1% |
| Voltage THD | < 2% |
| Output Receptacles | Hardwired - see manual for terminal block layout (8) IEC-320-C13 (2) IEC-320-C19 |
| Overload Capacity | 102-110% : 120s, 110-125%: 60s, 125-150%: 10s, >150%: 500ms |
| Efficiency (Normal Mode) | Up to 94% in Online mode, 98% in Hi-Efficiency mode |
| Output Frequency | 50/60 Hz autoselect, frequency converter as standard |
| Load Crest Factor | 3:1 |
| Battery | |
| Runtime (Minutes) Load (Watts) Battery runtimes are approximate and may vary with equipment, configuration, battery age, temperature, etc. Actual runtime may vary from +/- 15% around these typical values Show: Hover over graph for detailed runtime values | |
| Battery Management | ABM® and Temperature compensated charging method (user selectable), automatic battery test, deep discharge protection, automatic recognition of external battery units. |
| Extended Battery Capability | EBM (3U) |
| Communications | |
| User Interface | Multilingual graphical LCD display |
| Communication Ports | 1 USB port, 1 RS232 serial port (USB and RS232 ports cannot be used simultaneously), 4 dry contacts (DB9), 1 mini terminal block for remote On/Off and 1 for remote power Off, 1 DB15 for parallel operation |
| Communication Slot | 1 slot for Network-MS card, ModBus-MS or Relay-MS cards. |
| Environmental & Standards | |
| Audible Noise | <45dB |
| Operating Temperature | 0 to 40°C continuous |
| Safety markings | IEC/EN 62040-1, UL 1778, CSA 22.2 |
| EMC Markings | IEC/EN 62040 -2 , FCC Class A, IEC/EN 62040-3 (Performance) |
| Approvals | CE, CB report (TUV), UL |