| Technical Data | ||
| Model | CE4880-EU-180-H | CE48100-EU-200-H |
| AC Charge | ||
| Battery Type | Lithium-ion/Lead-acid/User Define | |
| Max. AC Charge Current (A) | 100 | |
| Charge Voltage Range (Vdc) | 40~60 | |
| Short Circuit Protection | Circuit breaker and blown fuse | |
| Solar Charge | ||
| Max. PV Open Circuit Voltage (Vdc) | 500 | |
| MPPT Voltage Range (Vdc) | 120~425 | |
| Number of PV MPPT Tracker | 2 | |
| Max. PV Input Power (W) | 5,500+5,500 | |
| Max. PV Input Current (A) | 22+22 | |
| Max. PV Charge Current (A) | 180 | 200 |
| Max. Hybrid Charge Current (A) | 180 | 200 |
| Charge Short Circuit Protection | Blown fuse | |
| Wiring Protection | Inverse wiring protection | |
| AC Input | ||
| Rated Input Voltage (Vac) | 230 (Single phase) | |
| Input Voltage Range (Vac) | 170~280 | |
| Frequency (Hz) | 50/60 | |
| Frequency Range (Hz) | 47±0.3~55±0.3 (50)/57±0.3~65±0.3 (60) | |
| Overload/Short Circuit Protection | Breaker | |
| Efficiency | >95% | |
| Conversion Time (bypass and inverter) | 10ms (Typical value) | |
| AC Reverse Protection | Yes | |
| Max. Bypass Overload Current (A) | 63 | |
| AC Output | ||
| Output Voltage Waveform | Pure sine wave | |
| Rated Output Power(W) | 8,000 | 10,000 |
| Power Factor | 1 | |
| Rated Output Voltage (Vac) | 230 (Single phase) | |
| Output Voltage Error | ±5% | |
| Output Frequency Range (Hz) | 50±0.3 / 60±0.3 | |
| Max. Efficiency | >92% | |
| Overload Protection | (102% < load <110%) ±10%: report error and turn off the output after5 minutes; (110% < load < 125%) ± 10%: report error and turn off the output after 10 seconds; Load >125% ±10%: report error and turn offthe output after 5 seconds; | |
| Peak Power (VA) | 16,000 | 20,000 |
| Loaded Motor Capacity (HP) | 5 | 10 |
| Output Short Circuit Protection | Breaker | |
| Bypass Breaker Specifications (A) | 63 | |
| Rated Battery Input Voltage (Vdc) | 48 (Minimum starting voltage 44) | |
| Battery Voltage Range (Vdc) | 40.0~60 ± 0.6 (Undervoltage alarm/shutdown voltage/overvoltage alarm/overvoltage recovery settable on LCD screen) | |
| General | ||
| Certification | IEC62109, EN61000 | |
| Operation Temperature Range (°C) | -15~55 | |
| Storage Temperature Range (°C) | -25~60 | |
| Humidity Range | 5%~95% (Conformal coating protection) | |
| Noise (dB) | < 60 | |
| Heat Dissipation | Forced air cooling, variable speed of fan | |
| Communication Interface | USB/RS485/dry node control | |
| Size (mm) | 620L×445W×130D | |
| Weight (kg) | 27 | |